utilisation category |
AC-3 |
|
---|
poles description |
3P |
|
---|
pole contact composition |
3 NO |
|
---|
System Voltage |
690 V AC 50/60 Hz power circuit
<= 690 V AC 50/60 Hz signalling circuit |
|
---|
[Ie] rated operational current |
20 A at 400 V AC AC-1 for power circuit
16 A at <= 440 V AC AC-3 power circuit |
|
---|
control circuit type |
AC 50/60 Hz |
|
---|
[Uc] control circuit voltage |
110 V AC 50/60 Hz |
|
---|
motor power kW |
4 kW at 220...230 V AC 50/60 Hz
4 kW at 480 V AC 50/60 Hz
4 kW at 500...600 V AC 50/60 Hz
4 kW at 660...690 V AC 50/60 Hz
7.5 kW at 380...415 V AC 50/60 Hz
5.5 kW at 440 V AC 50/60 Hz |
|
---|
auxiliary contact composition |
1 NO |
|
---|
[Uimp] rated impulse withstand voltage |
8 kV |
|
---|
overvoltage category |
III |
|
---|
[Ith] conventional free air thermal current |
20 A at <= 122 °F (50 °C) power circuit
10 A at <= 122 °F (50 °C) signalling circuit |
|
---|
Irms rated making capacity |
110 A AC signalling circuit conforming to IEC 60947
160 A AC power circuit conforming to NF C 63-110
160 A AC power circuit conforming to IEC 60947 |
|
---|
rated breaking capacity |
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947 |
|
---|
[Icw] rated short-time withstand current |
25 A <= 50 °C >= 15 min power circuit
80 A 1 s signalling circuit
90 A 500 ms signalling circuit
110 A 100 ms signalling circuit
115 A <= 122 °F (50 °C) 1 s power circuit
105 A <= 122 °F (50 °C) 5 s power circuit
100 A <= 122 °F (50 °C) 10 s power circuit
75 A <= 122 °F (50 °C) 30 s power circuit
55 A <= 122 °F (50 °C) 1 min power circuit
50 A <= 122 °F (50 °C) 3 min power circuit |
|
---|
associated fuse rating |
25 A gG at <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit conforming to IEC 60947
10 A gG signalling circuit conforming to VDE 0660 |
|
---|
average impedance |
3 mOhm at 50 Hz - Ith 20 A power circuit |
|
---|
[Ui] rated insulation voltage |
690 V signalling circuit conforming to IEC 60947-4-1
690 V signalling circuit conforming to IEC 60947-5-1
600 V signalling circuit conforming to UL 508
600 V power circuit conforming to CSA C22.2 No 14
600 V signalling circuit conforming to CSA C22.2 No 14
690 V power circuit conforming to IEC 60947-4-1
600 V power circuit conforming to UL 508 |
|
---|
insulation resistance |
> 10 MOhm signalling circuit |
|
---|
inrush power in VA |
30 VA at 68 °F (20 °C) |
|
---|
hold-in power consumption in VA |
4.5 VA at 68 °F (20 °C) |
|
---|
heat dissipation |
1.3 W |
|
---|
control circuit voltage limits |
0.2...0.75 Uc at <= 122 °F (50 °C) drop-out
0.8...1.15 Uc at <= 122 °F (50 °C) operational |
|
---|
connections - terminals |
Screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
Screw clamp terminals 1 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible - without cable end
Screw clamp terminals 1 cable(s) 0...0 in² (0.34...2.5 mm²) - cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
Screw clamp terminals 2 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible - without cable end
Screw clamp terminals 2 cable(s) 0...0 in² (0.34...1.5 mm²) - cable stiffness: flexible - with cable end |
|
---|
operating rate |
3600 cyc/h |
|
---|
auxiliary contacts type |
Type instantaneous (1 NO) |
|
---|
signalling circuit frequency |
<= 400 Hz |
|
---|
minimum switching current |
5 mA signalling circuit |
|
---|
minimum switching voltage |
17 V signalling circuit |
|
---|
mounting support |
Plate
Rail |
|
---|
tightening torque |
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm |
|
---|
operating time |
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing |
|
---|
safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
---|
non overlap distance |
0.02 in (0.5 mm) |
|
---|
mechanical durability |
10 Mcycles |
|
---|
electrical durability |
1.3 Mcycles 16 A AC-3 at Ue <= 440 V |
|
---|
mechanical robustness |
Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6 |
|
---|
depth |
2.24 in (57 mm) |
|
---|
product weight |
0.4 lb(US) (0.18 kg) |
|
---|